Genset Main Technical Data | ||||||||||||||||||
Genset Model | MC688YC | |||||||||||||||||
Prime Power | 500kW | |||||||||||||||||
Standby Power | 550KW | |||||||||||||||||
Frequency/Speed | 50Hz/1500rpm | |||||||||||||||||
Standard Voltage | 230/400V, Others as Application Requested | |||||||||||||||||
Phases | Three phases, four wires | |||||||||||||||||
Dimensions(L×W×H)mm | Open/Silent dimension as below list | |||||||||||||||||
100% Fuel Cons. (L/H) | 139.2-150 | |||||||||||||||||
Base Fuel tank (hour) | 8~10 |
Alternator Specifications | ||||||||||||||||||
Alternator Model | MECCA | |||||||||||||||||
Output power | 16kW-660kW | |||||||||||||||||
Voltage control | AVR | |||||||||||||||||
Number of phase | 3 | |||||||||||||||||
Power factor (Cos Phi) | 0.8 | |||||||||||||||||
Insulation Class | H | |||||||||||||||||
Number of Wires | 6 | |||||||||||||||||
Protection | 23 | |||||||||||||||||
Altitude | ≤ 1000 m | |||||||||||||||||
Number of Pole | 4 | |||||||||||||||||
Exciter type | AREP | |||||||||||||||||
Voltage regulation | ±0.5% | |||||||||||||||||
Totale Harmonic distortion | at no load < 4 % - on load < 4 % | |||||||||||||||||
Bearing | Single | |||||||||||||||||
Coupling | Direct |
Alternator Data | ||||||||||||||||||
♦ Operate either 50Hz or 60Hz. | ♦Stator grease insulation covered | |||||||||||||||||
♦ Standard enclosure IP23, but IP44, IP55 for option | ♦Rotator and excitation high polymer | |||||||||||||||||
♦ Insulation class H. | ♦ Resist the corruption oil and acid | |||||||||||||||||
♦ Shunt excitataion systems. | ♦Rotator balance is in accordance with BS5625 | |||||||||||||||||
♦ AREP or PMG system for options. | standard 12.5 | |||||||||||||||||
♦ Automatic voltage regulator | ♦High-quality lubrication sealed long-time bearing | |||||||||||||||||
♦ Single bearing alternator | ♦Rotator silicon steel close tight |
Model | LTP | PRP | Engine | Fuel Cons. | Cylinder | Displacement | Gov. | |||
KVA / KW | KVA/KW | Model | Origin | L/H(100%) | L | |||||
MC47YC | 47 | 37 | 42.5 | 34 | YC4D60-D21 | CN | 11.4 | 4L/NA | 4.2 | M/E |
MC69YC | 69 | 55 | 62.5 | 50 | YC4D85Z-D20 | CN | 15.0 | 4L/TC | 4.2 | M/E |
MC69YC | 69 | 55 | 62.5 | 50 | YC4D90Z-D21 | CN | 16.4 | 4L/TC | 4.2 | M/E |
MC83YC | 83 | 66 | 75 | 60 | YC4D100Z-D20 | CN | 18.0 | 4L/TC | 4.2 | M/E |
MC88YC | 88 | 70 | 80 | 64 | YC4A100Z-D20 | CN | 17.0 | 4L/TC | 4.8 | M/E |
MC110YC | 110 | 88 | 100 | 80 | YC6B135Z-D20 | CN | 21.1 | 6L/TC | 6.9 | M/E |
MC110YC | 110 | 88 | 100 | 80 | YC4A140L-D20 | CN | 23.1 | 4L/TCA | 4.8 | E |
MC124YC | 124 | 99 | 112.5 | 90 | YC6B155L-D21 | CN | 24.0 | 6L/TCA | 6.9 | M/E |
MC138YC | 138 | 110 | 125 | 100 | YC6B180L-D20 | CN | 28.0 | 6L/TCA | 6.9 | M/E |
MC165YC | 165 | 132 | 150 | 120 | YC6B205L-D20 | CN | 32.2 | 6L/TCA | 6.9 | E |
MC193YC | 193 | 154 | 175 | 140 | YC6A230L-D20 | CN | 35.9 | 6L/TCA | 7.3 | M/E |
MC206YC | 206 | 165 | 187.5 | 150 | YC6A245L-D21 | CN | 38.3 | 6L/TCA | 7.3 | E |
MC248YC | 248 | 198 | 225 | 180 | YC6MK285L-D20 | CN | 43.4 | 6L/TCA | 10.3 | M/E |
MC275YC | 275 | 220 | 250 | 200 | YC6MK350L-D20 | CN | 53.7 | 6L/TCA | 10.3 | M/E |
MC344YC | 344 | 275 | 312.5 | 250 | YC6MK420L-D20 | CN | 64.2 | 6L/TCA | 10.3 | E |
MC385YC | 385 | 308 | 350 | 280 | YC6MJ480L-D20 | CN | 82.1 | 6L/TCA | 11.7 | E |
MC413YC | 413 | 330 | 375 | 300 | YC6K500-D31 | CN | 80.9 | 6L/TCA | 12.2 | HPCR |
MC440YC | 440 | 352 | 400 | 320 | YC6T550L-D21 | CN | 84.1 | 6L/TCA | 16.4 | E |
MC481YC | 481 | 385 | 437.5 | 350 | YC6K570-D30 | CN | 96.3 | 6L/TCA | 12.9 | HPCR |
MC495YC | 495 | 396 | 450 | 360 | YC6T600L-D22 | CN | 91.6 | 6L/TCA | 16.4 | E |
MC550YC | 550 | 440 | 500 | 400 | YC6T660L-D20 | CN | 100.8 | 6L/TCA | 16.4 | E |
MC619YC | 619 | 495 | 562.5 | 450 | YC6TD780L-D20 | CN | 139.2 | 6L/TCA | 19.6 | ECM |
MC688YC | 688 | 550 | 625 | 500 | YC6TD840L-D20 | CN | 150.0 | 6L/TCA | 19.6 | ECM |
MC756YC | 756 | 605 | 687.5 | 550 | YC6TD900-D31 | CN | 151.2 | 6L/TCA | 19.6 | ECM |
MC825YC | 825 | 660 | 750 | 600 | YC6TD1000-D31 | CN | 167.0 | 6L/TCA | 19.6 | ECM |
MC825YC | 825 | 660 | 750 | 600 | YC6C1020L-D20 | CN | 178.1 | 6L/TCA | 39.6 | E |
MC894YC | 894 | 715 | 812.5 | 650 | YC6C1070L-D20 | CN | 187.2 | 6L/TCA | 39.6 | E |
MC963YC | 963 | 770 | 875 | 700 | YC6C1220L-D20 | CN | 213.4 | 6L/TCA | 39.6 | ECM |
MC1100YC | 1100 | 880 | 1000 | 800 | YC6C1320L-D20 | CN | 230.4 | 6L/TCA | 39.6 | ECM |
MC1375YC | 1375 | 1100 | 1250 | 1000 | YC12VC1680-D31 | CN | 266.4 | 12V/TCA | 79.17 | ECM |
MC1650YC | 1650 | 1320 | 1500 | 1200 | YC12VC2070-D31 | CN | 327.7 | 12V/TCA | 79.17 | ECM |
MC1925YC | 1925 | 1540 | 1750 | 1400 | YC12VC2270-D31 | CN | 361.5 | 12V/TCA | 79.17 | ECM |
MC2063YC | 2063 | 1650 | 1875 | 1500 | YC12VC2510-D31 | CN | 397.8 | 12V/TCA | 79.17 | ECM |
MC2200YC | 2200 | 1760 | 2000 | 1600 | YC12VC2700-D31 | CN | 428.6 | 12V/TCA | 79.17 | ECM |
MC2475YC | 2475 | 1980 | 2250 | 1800 | YC16VC3000-D31 | CN | 405.0 | 16V/TCA | 105.56 | ECM |
MC2750YC | 2750 | 2200 | 2500 | 2000 | YC16VC3300-D31 | CN | 527.6 | 16V/TCA | 105.56 | ECM |
MC3025YC | 3025 | 2420 | 2750 | 2200 | YC16VC3600-D31 | CN | 569.7 | 16V/TCA | 105.56 | ECM |
Icon | Indicator Light | Reason | Fault Analysis |
Low oil pressure alarm |
Low oil pressure alarm |
When oil pressure does not reduce normally, the light is on. |
-General because of a lack of oil or lubrication system failure caused by (refueling or replacing the oil filter) -When occurs this fault should automatically shutdown generator sets immediately. |
High water temperature alarm |
High water temperature alarm |
When the water temperature has risen to a level higher than or equal to the sensor setting, the light is on. |
-General because of a lack of water or oil shortage, or overload. -When occurs this fault should automatically shutdown generator sets immediately. |
Low fuel level alarm |
Low fuel level alarm |
When a fuel level has been detected by the sensor fitted to the daily tank, the light is on. |
-General because of a lack of water or oil shortage, or overload. -When occurs this fault should automatically shutdown generator sets immediately. |
Battery charger fault alarm |
Battery charger fault alarm |
If the charging system has fault, when engine running, the light is off. |
-Battery charging system fault caused. -The light is on at the initial start, when the charger reaches a certain speed, the light is off. -This failure will not lead to automatic shutdown generating units. |
Crank failure alarm |
Crank failure alarm |
When the generator set failed three times (or six times) in a row starting, the light is on. |
-Oil supply system or re-start the system failure caused. |
Overload or breaker tripping alarm |
Overload or breaker tripping alarm |
When overloading or Short circuit, the light is on. Tripping circuit breakers cause generator set load out. |
-In this fault, it need to load or unload some parts to eliminate short-circuit, and then re-close the circuit breaker. |